Changes

Jump to navigation Jump to search
Line 19: Line 19:  
== Manometer & Troubleshooting Filter/Suction Problems ==
 
== Manometer & Troubleshooting Filter/Suction Problems ==
   −
A monometer has been installed on the output elbow of the dust collector. This manometer measures positive static pressure from the exhaust of the impeller due to the impedance of the filter. Static pressure with a clean filter during regular usage is should not be more than 2" WC ([https://en.wikipedia.org/wiki/Inch_of_water| water column] is the difference, in inches, between the height of the water level in either leg of the tube of water).  
+
A manometer has been installed on the output elbow of the dust collector. This manometer measures positive static pressure from the exhaust of the impeller due to the impedance of the filter. Static pressure with a clean filter during regular usage should not be more than 2" WC ([https://en.wikipedia.org/wiki/Inch_of_water| water column] is the difference, in inches, between the height of the water level in either leg of the tube of water).  
   −
The filter is blocked when the pressure is higher than 2" WC, and needs to be cleaned. If above 2" WC, overall system suction is reduced and the dust collector will not collect sawdust from the rest of the system appropriately, is a health hazard, and gets fine dust over everything.
+
The filter is blocked when the pressure is higher than 2" WC, and needs to be cleaned. If above 2" WC, overall system suction is reduced and the dust collector will not collect sawdust from the rest of the system appropriately, is a health hazard, and gets fine dust over everything.
    
== How To ==
 
== How To ==
Domain Admins
586

edits

Cookies help us deliver our services. By using our services, you agree to our use of cookies.

Navigation menu