Boiler room circuits. PP1-1 scares me
Line 8: Line 8:     
Back of the shop by the loading dock. Can't miss it.
 
Back of the shop by the loading dock. Can't miss it.
 +
 +
Lots of sketchy shit in this one.
 +
 +
Single phase and 2 pole circuits wired to 3 phase breakers. One apparent circuit wired to 2 panels.
 +
 +
Several high amp 3 phase breakers that are unmapped.
 +
 +
 +
 +
{|Class="wikitable sortable" border="1" style="td { border: 1px solid #000000}"
 +
|-
 +
! Breaker # !! Used !! What Is It
 +
|-
 +
| 14&16&18 || unused || 3 phase, 20 amp, 3 black. Wiring trough, boiler room. Possible dust collection circuit thru existing disconnect.
 +
|-
 +
| 19&16&18 || used || 2-120v circuits on a 3 phase breaker. Blue wires. Boiler & zone pumps, this is bad and wrong.
 +
|-
 +
| 22 || unused || this is a stray 208v single red wire on a 3 phase breaker that runs to a 3 phase disconnect in the boiler room. Should be disconnected and abandoned.(used to be paired with wires pp1-2 # 35&37)
 +
|-
 +
|}
    
'''PP1-2'''
 
'''PP1-2'''
Line 27: Line 47:  
|26 || yes, works || Currently connected to the entire east wall. This includes dust collector and Clausing electronics. Please do not connect chop saw table to east wall while others are working.
 
|26 || yes, works || Currently connected to the entire east wall. This includes dust collector and Clausing electronics. Please do not connect chop saw table to east wall while others are working.
 
|-
 
|-
 +
| 35&37 || used || 40 amp 1 phase 240v thru a 3 phase disconect used as junction box to another 3 phase disconnect used as a 1 phase 35 amp disconnect. Compressor.
 
|}
 
|}
  