Line 9: Line 9:  
Back of the shop by the loading dock. Can't miss it.
 
Back of the shop by the loading dock. Can't miss it.
   −
Lots of sketchy shit in this one.
+
Some sketchy shit in this one.
   −
Single phase and 2 pole circuits wired to 3 phase breakers. One apparent circuit wired to 2 panels.
+
Single phase and 2 pole circuits wired to 3 phase breakers.
    
Several high amp 3 phase breakers that are unmapped.
 
Several high amp 3 phase breakers that are unmapped.
Line 21: Line 21:  
! Breaker # !! Used !! What Is It
 
! Breaker # !! Used !! What Is It
 
|-
 
|-
| 14&16&18 || unused || 3 phase, 20 amp, 3 black. Wiring trough, boiler room. Possible dust collection circuit thru existing disconnect.
+
| 14&16&18 || unused || 3 phase, 20 amp, 3 black. Wiring trough, boiler room. Dust collection circuit thru existing disconnect.
 
|-
 
|-
 
| 19&16&18 || used || 2-120v circuits on a 3 phase breaker. Blue wires. Boiler & zone pumps, this is bad and wrong.
 
| 19&16&18 || used || 2-120v circuits on a 3 phase breaker. Blue wires. Boiler & zone pumps, this is bad and wrong.
 
|-
 
|-
| 22 || unused || this is a stray 208v single red wire on a 3 phase breaker that runs to a 3 phase disconnect in the boiler room. Should be disconnected and abandoned.(used to be paired with wires pp1-2 # 35&37)
+
| 22 || unused || this is a stray 208v single red wire on a 3 phase breaker that runs to wiring troughin the boiler room. Should be disconnected and abandoned.(used to be paired with wires pp1-2 # 35&37)
 
|-
 
|-
 
|}
 
|}
Line 47: Line 47:  
|26 || yes, works || Currently connected to the entire east wall. This includes dust collector and Clausing electronics. Please do not connect chop saw table to east wall while others are working.
 
|26 || yes, works || Currently connected to the entire east wall. This includes dust collector and Clausing electronics. Please do not connect chop saw table to east wall while others are working.
 
|-
 
|-
| 35&37 || used || 40 amp 1 phase 240v thru a 3 phase disconect used as junction box to another 3 phase disconnect used as a 1 phase 35 amp disconnect. Compressor.
+
| 35&37 || used || Compressor 40 amp 1 phase 240v thru a 35 amp disconnect in boiler room.
 
|}
 
|}
   Line 173: Line 173:  
|-
 
|-
 
| 18 || yes. works. || Shop heating radiator fans and thermostats.
 
| 18 || yes. works. || Shop heating radiator fans and thermostats.
|-
+
| 20 || yes. works. || Outlet in closet
| 20 || yes. works. || Outlet in closet - By extension, WiFi
   
|-
 
|-
 
|}
 
|}