Electrical
Power Panels
If you find out what a circuit breaker does, make sure it's numbered in the box and that information about what it powers ends up here. If possible, label the outlet box as well. What form this document takes remains to be seen; hopefully we will get a solid amount of information into it so further work on our electrical system won't totally be explorative.
First Floor
PP1-1
Back of the shop by the loading dock. Can't miss it.
Lots of sketchy shit in this one.
Single phase and 2 pole circuits wired to 3 phase breakers. One apparent circuit wired to 2 panels.
Several high amp 3 phase breakers that are unmapped.
Breaker # | Used | What Is It |
---|---|---|
14&16&18 | unused | 3 phase, 20 amp, 3 black. Wiring trough, boiler room. Possible dust collection circuit thru existing disconnect. |
19&16&18 | used | 2-120v circuits on a 3 phase breaker. Blue wires. Boiler & zone pumps, this is bad and wrong. |
22 | unused | this is a stray 208v single red wire on a 3 phase breaker that runs to a 3 phase disconnect in the boiler room. Should be disconnected and abandoned.(used to be paired with wires pp1-2 # 35&37) |
PP1-2
Back of the shop by the loading dock. Can't miss it.
Breaker # | Used | What Is It |
---|---|---|
6 | Yes, works | 20amp, 2 outlets hot metal side of furnace room, short drop near center of shop. Light in the boiler room. |
8 | Yes, works | 20 amp, outlet at hot metal side of furnace room, possibly second outlet behind lockers. |
7,9,11 | yes. works. | Power to chiller/heat pump on the roof for AC... and also the air handler under it inside. The |
25 | yes , works | Lights at catwalk and kitchen, outlet at kitchen fridge. |
26 | yes, works | Currently connected to the entire east wall. This includes dust collector and Clausing electronics. Please do not connect chop saw table to east wall while others are working. |
35&37 | used | 40 amp 1 phase 240v thru a 3 phase disconect used as junction box to another 3 phase disconnect used as a 1 phase 35 amp disconnect. Compressor. |
Small fuse box
Back of the shop, left of PP1-1, above the light switches.
Left fuse, exit signs.
PB1-1
An unremarkable box full of wires.
PB1-2
Power box connected to PP1-1 by conduit. Bridges the A/C heat pump/air handler circuit, among other things. The 3-phase for A/c heat pump and air handler is bridged such that the entire 3 phase comes from PP1-1 up to the roof via PB1-2, and a branch switched on the roof by relay comes back down in the same conduit that goes the the roof. This circuit is passed via conduit to the air handler, and switched manually on the bottom of the air handler.
PP1-3
Metal shop, by the lathes.
Breaker # | Used | What Is It |
---|---|---|
1, a&b | yes, works | 20 amp. |
3, a&b | ? | |
5&7, a&b | yes, works | 50 amp, 240v, cold metal. |
5b & 7a | yes works | 20 amp 240v, dedicated Clausing lathe. |
PP1-4
In the tool cage.
Breaker # | Used | What Is It |
---|---|---|
18&20 | yes, works | 50 amp, 240v, hot metal at welding area. |
24&26 | yes, works | 15 amp, 240v, shopbot. |
37 | yes, works | 20 amp, 120v, hot metal at welding area. |
PP1-5
Cold Metal shop,
Breaker # | Used | What Is It |
---|---|---|
1 | in use | landlord circuit, don't touch |
2 | in use | landlord circuit, don't touch |
3 | in use | landlord circuit, don't touch |
4 | in use | landlord circuit, don't touch |
5 | in use | landlord circuit, don't touch |
6 | in use | landlord circuit, don't touch |
7 | in use | landlord circuit, don't touch |
8 | in use | landlord circuit, don't touch |
9 | ||
10 | ||
11 | ||
12 | ||
13 | ||
14 | ||
15 | ||
16 | in use | kitchen, above counter outlets. |
17 | ||
18 | in use | 3 outlets, metal shop side of kitchen wall. |
19 | ||
20 |
PP1-6
In the safe in the lounge.
Breaker # | Used | What Is It |
---|---|---|
1 | yes. works. | Lounge Everything. Upstairs bathroom for reasons unknown. |
TODO: take down notes from tape in the box, mark them in table above
PP1-7
Blue fuse box in the furnace room. Powers just the air compressor.
Second Floor
PP2-1
In the AC/comms closet upstairs.
Breaker # | Used | What Is It |
---|---|---|
18 | yes. works. | Shop heating radiator fans and thermostats. |
20 | yes. works. | Outlet in closet |
PP2-2
On the catwalk.
This is a 3 phase panel,"High Leg Delta" configuration, http://en.wikipedia.org/wiki/High-leg_delta The center bus bar is 208v to neutral.
Breaker # | Used | What Is It |
---|---|---|
1 | in use | 20 amp,above kitchen ceiling, servers on catwalk |
2 | in use | 20 amp, 2 lower outlets, in kitchen either side of door. Outlet at SEM location |
3 | Not used | 208 volts to neutral, not recommended for use except in 3 phase circuit. |
4 | Not used | 208 volts to neutral, not recommended for use except in 3 phase circuit. |
5 | in use | split 20 amp breaker, 2 circuits a&b, Beer church. |
6 | in use | paired with #8, 20 amp 240v, Oven, 8 gauge, 4 wires, capable of 50 amps |
7 | in use | ? |
8 | in use | paired with #6, 20 amp 240v, Oven, 8 gauge, 4 wires, capable of 50 amps |
9 | Not used | 208 volts to neutral, not recommended for use except in 3 phase circuit. |
10 | Not used | 208 volts to neutral, not recommended for use except in 3 phase circuit. |
11 | in use | 20 amp, Laser |
12 | in use | paired with # 14, 20 amp 240v, kitchen,above counter. For induction cook top |
13 | ||
14 | in use | paired with # 12, 20 amp 240v, kitchen,above counter. For induction cook top |
15 | ||
16 | Not used | 208 volts to neutral, not recommended for use except in 3 phase circuit. |
17 | ||
18 | in use | 20 amp, Outlet at SEM location |
Electrical Punch List
Desired Circuits
Hot Metals
Wood Shop
drops: http://www.mcmaster.com/#4804k12/=pmf353 ??
Other goodies
100 amp 5 wire 3 phase disconnect with lugs sufficient for #1 feeder cable. This could be located anywhere that is convenient.